Substation
Template:Short description Script error: No such module "other uses".
Page Module:Message box/ambox.css has no content.
This article needs additional citations for verification. (May 2025) |
- Primary power lines' side
- Secondary power lines' side
- Primary power lines
- Ground wire
- Overhead lines
- Potential transformer
- Disconnect switch
- Circuit breaker
- Current transformer
- Lightning arrester
- Main transformer
- Control building
- Security fence
- Secondary power lines
A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and the consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. As of 2002, there were approximately 55,000 substations in the United States.[2] Substations are also occasionally known in some countries as switchyards.
Substations may be owned and operated by an electrical utility, or may be owned by a large industrial or commercial customer. Generally substations are unattended, relying on SCADA for remote supervision and control.
The word substation comes from the days before the distribution system became a grid. As central generation stations became larger, smaller generating plants were converted to distribution stations, receiving their energy supply from a larger plant instead of using their own generators. The first substations were connected to only one power station, where the generators were housed, and were subsidiaries of that power station.
Construction
Substations may be designed and built by a contractor or alternately all phases of its development may be handled by the electrical utility. Most commonly, the utility does the engineering and procurement while hiring a contractor for actual construction.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Major design constraints for construction of substations include land availability and cost, limitations on the construction period, transportation restrictions, and the need to get the substation running quickly.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Prefabrication is a common way to reduce the construction cost.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. For connecting the new substation, a partial outage at another substation may be required, but the utility often tries to minimize downtime.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Types
Substations typically serve at least one of the following purposes:Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Increasing the voltage produced by electric power generation for efficient transmission over long distances, using step-up transformersLua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Interconnection of different power gridsLua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Reducing the voltage from transmission to lower-voltage distribution lines that supply individual homes or businessesLua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Converting from alternating current (AC) to direct current (DC)Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Transmission substation
A transmission substation connects two or more transmission lines.[3] The simplest case is where all transmission lines have the same voltage. In such cases, substation contains high-voltage switches that allow lines to be connected or isolated for fault clearance or maintenance. A transmission station may have transformers to convert between two transmission voltages, voltage control/power factor correction devices such as capacitors, reactors or static VAR compensators and equipment such as phase shifting transformers to control power flow between two adjacent power systems.
Transmission substations can range from simple to complex. A small "switching station" may be little more than a bus plus some circuit breakers. The largest transmission substations can cover a large area (several acres/hectares) with multiple voltage levels, many circuit breakers, and a large amount of protection and control equipment (voltage and current transformers, relays and SCADA systems). Modern substations may be implemented using international standards such as IEC Standard 61850.
Distribution substation
A distribution substation transfers power from the transmission system to the distribution system of an area.[3] It is uneconomical to directly connect electricity consumers to the main transmission network, unless they use large amounts of power, so the distribution station reduces voltage to a level suitable for local distribution.
The input for a distribution substation is typically at least two transmission or sub-transmission lines. Input voltage may be, for example, 115 kV, or whatever is common in the area. The output is a number of feeders. Distribution voltages are typically medium voltage, between 2.4 kV and 33 kV, depending on the size of the area served and the practices of the local utility. The feeders run along streets overhead (or underground, in some cases) and power the distribution transformers at or near the customer premises.
In addition to transforming voltage, distribution substations also isolate faults in either the transmission or distribution systems. Distribution substations are typically the points of voltage regulation, although on long distribution circuits (of several miles/kilometers), voltage regulation equipment may also be installed along the line.
The downtown areas of large cities feature complicated distribution substations, with high-voltage switching, and switching and backup systems on the low-voltage side. More typical distribution substations have a switch, one transformer, and minimal facilities on the low-voltage side.
Collector substation
In distributed generation projects such as a wind farm or photovoltaic power station, a collector substation may be required. It resembles a distribution substation although power flow is in the opposite direction, from many wind turbines or inverters up into the transmission grid. Usually for economy of construction the collector system operates around 35 kV, although some collector systems are 12 kV, and the collector substation steps up voltage to a transmission voltage for the grid. The collector substation can also provide power factor correction if it is needed, metering, and control of the wind farm. In some special cases a collector substation can also contain an HVDC converter station.
Collector substations also exist where multiple thermal or hydroelectric power plants of comparable output power are in proximity. Examples for such substations are Brauweiler in Germany and Hradec in the Czech Republic, where power is collected from nearby lignite-fired power plants. If no transformers are required for increasing the voltage to transmission level, the substation is a switching station.
Converter substations
Converter substations may be associated with HVDC converter plants, traction current, or interconnected non-synchronous networks. These stations contain power electronic devices to change the frequency of current, or else convert from alternating to direct current or the reverse. Formerly rotary converters changed frequency to interconnect two systems; nowadays such substations are rare.
Switching station
A switching station is a substation without transformers and operating only at a single voltage level. Switching stations are sometimes used as collector and distribution stations. Sometimes they are used for switching the current to back-up lines or for parallelizing circuits in case of failure. An example is the switching stations for the Inga–Shaba HVDC transmission line.
A switching station may also be known as a switchyard, and these are commonly located directly adjacent to or nearby a power station. In this case the generators from the power station supply their power into the yard onto the generator bus on one side of the yard, and the transmission lines take their power from a Feeder Bus on the other side of the yard.
An important function performed by a substation is switching, which is the connecting and disconnecting of transmission lines or other components to and from the system. Switching events may be planned or unplanned. A transmission line or other component may need to be de-energized for maintenance or for new construction, for example, adding or removing a transmission line or a transformer. To maintain reliability of supply, companies aim at keeping the system up and running while performing maintenance. All work to be performed, from routine testing to adding entirely new substations, should be done while keeping the whole system running.
-
Switchyard at Grand Coulee Dam, United States, 2006. This is a 500 kV switchyard.
-
Former high-voltage substation in Stuttgart, Germany, now 110 kV switching station. The 220 kV level is eliminated for grid simplification.
-
230 kV High-voltage switching station in Washington, United States
Unplanned switching events are caused by a fault in a transmission line or any other component, for example:
The function of the switching station is to isolate the faulty portion of the system in the shortest possible time. De-energizing faulty equipment protects it from further damage, and isolating a fault helps keep the rest of the electrical grid operating with stability.[5]
Railways
Script error: No such module "Labelled list hatnote". Electrified railways also use substations, often distribution substations. In some cases a conversion of the current type takes place, commonly with rectifiers for direct current (DC) trains, or rotary converters for trains using alternating current (AC) at frequencies other than that of the public grid. Sometimes they are also transmission substations or collector substations if the railway network also operates its own grid and generators to supply the other stations.
Mobile substation
A mobile substation is a substation on wheels, containing a transformer, breakers and buswork mounted on a self-contained semi-trailer, meant to be pulled by a truck. They are designed to be compact for travel on public roads, and are used for temporary backup in times of natural disaster or war. Mobile substations are usually rated much lower than permanent installations, and may be built in several units to meet road travel limitations.[6]
Design
Substation design is aimed at minimizing cost while ensuring power availability and reliability, and enabling changes to the substation in the future.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Substations may be built outdoors, indoors, or underground or in a combination of these locations.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Location selection
Selection of the location of a substation must consider many factors. Sufficient land area is required for installation of equipment with necessary clearances for electrical safety, and for access to maintain large apparatus such as transformers. The site must have room for expansion due to load growth or planned transmission additions. Environmental effects of the substation must be considered, such as drainage, noise and road traffic effects.
The substation site must be reasonably central to the distribution area to be served. The site must be secure from intrusion by passers-by, both to protect people from injury by electric shock or arcs, and to protect the electrical system from misoperation due to vandalism.
If not owned and operated by a utility company, substations are typically occupied on a long lease such as a renewable 99-year lease, giving the utility company security of tenure.[7]
Design diagrams
The first step in planning a substation layout is the preparation of a single-line diagram, which shows in simplified form the switching and protection arrangement required, as well as the incoming supply lines and outgoing feeders or transmission lines. It is a usual practice by many electrical utilities to prepare one-line diagrams with principal elements (lines, switches, circuit breakers, transformers) arranged on the page similarly to the way the apparatus would be laid out in the actual station.[3]
In a common design, incoming lines have a disconnector and a circuit breaker. In some cases, the lines will not have both, with either a switch or a circuit breaker being all that is considered necessary. A disconnect switch is used to provide isolation, since it cannot interrupt load current. A circuit breaker is used as a protection device to interrupt fault currents automatically, and may be used to switch loads on and off, or to cut off a line when power is flowing in the 'wrong' direction. When a large fault current flows through the circuit breaker, this is detected through the use of current transformers. The magnitude of the current transformer outputs may be used to trip the circuit breaker resulting in a disconnection of the load supplied by the circuit break from the feeding point. This seeks to isolate the fault point from the rest of the system, and allow the rest of the system to continue operating with minimal impact. Both switches and circuit breakers may be operated locally (within the substation) or remotely from a supervisory control center.
With overhead transmission lines, the propagation of lightning and switching surges can cause insulation failures into substation equipment. Line entrance surge arrestors are used to protect substation equipment accordingly. Insulation Coordination studies are carried out extensively to ensure equipment failure (and associated outages) is minimal.
Once past the switching components, the lines of a given voltage connect to one or more buses. These are sets of busbars, usually in multiples of three, since three-phase electrical power distribution is largely universal around the world.
The arrangement of switches, circuit breakers, and buses used affects the cost and reliability of the substation. For important substations a ring bus, double bus, or so-called "breaker and a half" setup can be used, so that the failure of any one circuit breaker does not interrupt power to other circuits, and so that parts of the substation may be de-energized for maintenance and repairs. Substations feeding only a single industrial load may have minimal switching provisions, especially for small installations.[8]
Safety
Because of the risk of electrical shock, substations are inherently dangerous to electrical workers.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. To mitigate this hazard, substations are designed with various safety features.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Live conductors and bare equipment are kept separate, either with protected equipment, or using screens or distance.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Based on the jurisdiction or company,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. there are safety standards with minimum required clearance between different live equipment or conductors or between live metal and the ground, which often varies with higher clearance being required for higher voltages because of the greater ability to generate flashover.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. To this is added the necessary space for employees to work safely and vehicles to pass.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Sometimes it is necessary to work on parts of the substation while energized, but employees must maintain a safe distance of at least 3 metres (9.8 ft).Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. The aim to reduce substation footprints comes into conflict with ease of maintenance enhanced by including gaps where employees can safely work.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Underneath a substation, a mat or grid of conductors laid around 0.5 or 0.6 metres (1 ft 8 in or 2 ft 0 in) underground provides grounding.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. This grid, which is typically copper although it may be galvanized iron in some countries,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. is used to ground circuits that are being worked on to prevent accidental re-energization while workers are in contact with a de-energized circuit.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Often, earth rods are driven deeper into the ground from the grounding grid for lower resistance grounding,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. and may be surrounded by bentonite or marconite to further reduce resistance and ensure effective grounding for the lifetime of the substation.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Above ground, the grounding conductors may be steel, aluminum, or copper. They must be thick enough to carry the expected current of a fault for 1–3 seconds and remain undamaged.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Substation fences, typically at least 2 metres (6 ft 7 in) in height, both protect the public from electrical hazards and also protect the substation from vandalism.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Internal fences can also be incorporated to protect employees from areas that are unsafe when energized.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Components
Substations generally have switching, protection and control equipment, and transformers. In a large substation, circuit breakers are used to interrupt any short circuits or overload currents that may occur on the network. Smaller distribution stations may use recloser circuit breakers or fuses for protection of distribution circuits. Substations themselves do not usually have generators, although a power plant may have a substation nearby. Other devices such as capacitors, voltage regulators, and reactors may also be located at a substation.
Substations may be on the surface in fenced enclosures, underground, or special-purpose buildings. High-rise buildings may have several indoor substations. Indoor substations are usually found in urban areas to reduce the noise from transformers, improve appearance, or protect switchgear from extreme climate or pollution.
Substations often use busbars as conductors between electrical equipment. Busbars may be aluminum tubing 3–6 inches (76–152 mm) thick, or else wires (strain bus).Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Outdoor, above-ground substation structures include wood pole, lattice metal tower, and tubular metal structures, although other variants are available. Where space is plentiful and appearance of the station is not a factor, steel lattice towers provide low-cost supports for transmission lines and apparatus. Low-profile substations may be specified in suburban areas where appearance is more critical. Indoor substations may be gas insulated substations (GIS) (at high voltages, with gas insulated switchgear), or use metal-enclosed or metal-clad switchgear at lower voltages. Urban and suburban indoor substations may be finished on the outside so as to blend in with other buildings in the area.
A compact substation is generally an outdoor substation built in a metal enclosure, in which each item of the electrical equipment is located very near to each other to create a relatively smaller footprint size of the substation.
Switchgear
High-voltage circuit breakers are commonly used to interrupt the flow of current in substation equipment. At the time of interruption, current could be normal, too high due to excessive load, unusual due to a fault, or tripped by protective relays prior to anticipated trouble.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. The most common technologies to extinguish the power arc from separating the conductors in the breaker include:Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Air at atmospheric pressure (air-insulated switchgear (AIS)), which is the most common worldwide.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Air is the cheapest insulator and is easy to modify, but AIS takes up more space, and leaves equipment exposed to the outside environment.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. One drawback of AIS is the visual impact of a larger substation with overhead power lines entering and exiting, which may be unacceptable in scenic or urban areas.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. AIS requires additional bracing in a seismically active area, and emits more electromagnetic fields and noise than alternative technologies.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Gas (gas circuit breaker (GCB) or gas-insulated switchgear (GIS)), most commonly sulfur hexafluoride (SF6) or a mixture of gases including SF6.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Although it is the most expensive, these gases are a much more effective insulator than air.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. GIS require only 10 to 20 percent of the land area as AIS,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. which can save on land acquisition cost in urban areas,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. and allow the substation to be built at the exact location where its power is being used in an industrial or urban area—which can be a significant cost saving. On the generation side, GIS can be installed closer to the generator which allows cost savings in cabling, bus duct connections, and civil construction and can increase reliability.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. GIS can replace AIS if power requirements increase without requiring additional land area.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Additionally, GIS is commonly installed in an enclosed building that keeps the equipment protected from pollution and salt.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Unless the substation is often used for switching, maintenance cost can be very low or even zero for many years.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Because SF6 turns to solid around −40 °C (−40 °F), in some climates these circuit breakers require heaters to function in extremely cold weather.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. SF6 has been used in switchgear since the 1960s.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Mineral oil (called OCB for oil circuit breaker) provides a high resistance between the opened contacts, effectively stopping the flow of current.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Although oil circuit breakers are suitable for a wide range of voltages, the oil becomes contaminated during the suppression of arcs and must be filtered or replaced periodically.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Vacuum is a better insulator than air but less than gas or oil. Vacuum circuit breakers (VCB) are smaller than air circuit breakers and are commonly used in distribution and other switchgear under 35 kV.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
- Mixed, including both gas and air insulation. Although it’s the least common optionLua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. it can be useful when an air-insulated substation needs to be expanded but there is very limited location for additional construction.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Reclosers are similar to breakers, and can be cheaper because they do not require separate protective relays. Often used in distribution, they often are programmed to trip when the amps exceed a certain amount over a period of time. Reclosers will attempt to re-energize the circuit after a delay. If unsuccessful for a few times, the recloser will have to be manually reset by an electrical worker.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Capacitors
Capacitor banks are used in substations to balance the lagging current draw from inductive loads (such as motors, transformers, and some industrial equipment) with their reactive load.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Additional capacitor capacity may be needed if dispersed generation (such as small diesel generators, rooftop photovoltaic solar panels, or wind turbines) are added to the system.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Capacitors can reduce the current in wires, helping stem system losses from voltage drop or enabling extra power to be sent through the conductors. Capacitors may be left on in response to constant inductive load or turned on when inductive load is increased, such as in the summer for air conditioners. The switching may be remote and can be done manually or automatically.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Control rooms
Larger substations have control rooms for the equipment used to monitor, control, and protect the rest of the substation equipment. It often contains protective relays, meters, breaker controls, communications, batteries, and recorders that save detailed data about substation operations, particularly when there is any unusual activity, to help reconstruct what happened after the fact. These control rooms typically are heated and air conditioned to ensure the reliable operation of this equipment.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Additional equipment is necessary to handle power surges associated with intermittent renewable energy such as dispersed generation from wind or solar.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Transformers
Most transformers lose between 5 and 1.5 percent of their input as heat and noise. Iron losses are no-load and constant whenever the transformer is energized, while copper and auxiliary losses are proportionate to the square of the current. Auxiliary losses are due to running fans and pumpsLua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. which is noisy when the transformer is operating at maximum capacity.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. To reduce noise, enclosures are often built around the transformer and can also be added after the substation is built.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Oil-based transformers are often built with bunded areas to prevent the escape of flaming or leaking oil. Fire separation areas or firewalls are built around the transformer to stop the spread of fire.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. Firefighting vehicles are allowed a path to access the area.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Maintenance
Maintenance of substations involves inspections, data collection and analysis, and routine scheduled work. Using methods such as infrared scanning and dissolved gas analysis, it can be predicted when the substation will need maintenance and predict dangers before they materialize. Infrared technology finds hot spots in the substation where electrical energy is being converted to heat,Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found. which indicates a problem and can cause additional damage from the high heat. Dissolved gas analysis can tell when an oil-insulated transformer needs to have the oil filtered or replaced, and also detect other issues.Lua error in package.lua at line 80: module 'Module:Footnotes/anchor_id_list' not found.
Automation
Script error: No such module "Labelled list hatnote". Early electrical substations required manual switching or adjustment of equipment, and manual collection of data for load, energy consumption, and abnormal events. As the complexity of distribution networks grew, it became economically necessary to automate supervision and control of substations from a centrally attended point, to allow overall coordination in case of emergencies and to reduce operating costs. Early efforts to remote control substations used dedicated communication wires, often run alongside power circuits. Power-line carrier, microwave radio, fiber optic cables as well as dedicated wired remote control circuits have all been applied to Supervisory Control and Data Acquisition (SCADA) for substations. The development of the microprocessor made for an exponential increase in the number of points that could be economically controlled and monitored. Today, standardized communication protocols such as DNP3, IEC 61850 and Modbus, to list a few, are used to allow multiple intelligent electronic devices to communicate with each other and supervisory control centers. Distributed automatic control at substations is one element of the so-called smart grid.
References
Page Template:Reflist/styles.css has no content.
- ^ Page Module:Citation/CS1/styles.css has no content."Joint Consultation Paper: Western Metropolitan Melbourne Transmission Connection and Subtransmission Capacity". Jemena. Powercor Australia, Jemena, Australian Energy Market Operator. Retrieved 4 February 2016.
- ^ Page Module:Citation/CS1/styles.css has no content.Anguiano, Dani (10 December 2022). "Attacks on Pacific north-west power stations raise fears for US electric grid". The Guardian. Los Angeles. Retrieved 10 December 2022.
- ^ a b c Page Module:Citation/CS1/styles.css has no content.Stockton, Blaine. "Design Guide for Rural Substations" (PDF). USDA Rural Development. United States Department of Agriculture. Retrieved 4 February 2016.
- ^ Page Module:Citation/CS1/styles.css has no content.Steinberg, Neil (13 December 2013). "Lights On but Nobody Home: Behind the Fake Buildings that Power Chicago". Retrieved 14 December 2013.
- ^ Page Module:Citation/CS1/styles.css has no content."Transformer Fire Video". metacafe. User Eagle Eye. Retrieved 4 February 2016.
- ^ Page Module:Citation/CS1/styles.css has no content.Boyd, Dan; Rampaul, Glen. "Mobile Substations" (PDF). IEEE Winnipeg PES Chapter. IEEE Power and Energy Society. Retrieved 11 October 2017.
- ^ Chapman, A. and Broom, R., Electricity Substation Leases: Considerations for Utility Companies, Landowners and Developers, Squire Patton Boggs, originally published by Utility Week, 26 January 2018, accessed 22 August 2023
- ^ Donald G. Fink, H. Wayne Beatty Standard Handbook for Electrical Engineers Eleventh Edition, McGraw Hill 1978 Template:ISBN Chapter 17 Substation Design
Further reading
Page Module:Side box/styles.css has no content.Page Template:Sister project/styles.css has no content.
- Page Module:Citation/CS1/styles.css has no content.Blume, S.W. (2016). Electric Power System Basics for the Nonelectrical Professional. IEEE Press Series on Power and Energy Systems. Wiley. ISBN 978-1-119-18019-7.
- Page Module:Citation/CS1/styles.css has no content.Finn, John (2019). "Introduction to Substation Planning and Concepts". Substations. Springer International Publishing. pp. 7–10. ISBN 978-3-319-49574-3.
Lua error in package.lua at line 80: module 'Module:Navbox/configuration' not found. Lua error in package.lua at line 80: module 'Module:Authority control/config' not found.